|
» The "FAN" setting is selected at the air conditioner
thermostat...
Instead, it should always be set on "AUTO". Set to cool on FAN, the blower
pushes air through the ductwork continuously while the compressor cycles on and off. Moisture
removed from the air while the compressor runs is reintroduced to the house when the fan alone
runs between compressor cycles. Don't let this happen! Don't set the system on "FAN"!
Set to cool on AUTO, humidity is kept lower, costs are much lower and comfort is higher. If
your ducts are leaky (and most are) the FAN setting is especially costly to you.
» The air conditioner's air filter is clogged...Air flow
is restricted. When air flow is restricted your HVAC (Heating, Ventilating and Air Conditioning
) system runs less efficiently. A clogged filter increases costs, reduces comfort and can lead
to costly equipment failures. When air flow is severely restricted, ice grows on the air conditioner's
evaporator coils, a condition that can precede "slugging" the compressor with liquid
refrigerant. The resulting repair bill can exceed $1,000. Change the air filter religiously!
It should be replaced monthly during summer and winter periods of heavy use.
» The evaporator coils are clogged with accumulated dust...Air
flow is restricted. Problems that result are much like those described above for dirty filters.
If you have central air conditioning, all the air in your house draws through the air conditioner's
filter, then through the cooling (evaporator) coils. Generally the filter doesn't clean the
air; its purpose is to protect the equipment, in particular the cooling coils. In spite of
the filter the downstream coils gather dust and grime over time. Energy efficiency is degraded
by about 5% each year as the coils get dirtier! Your costs go up while comfort goes down. Have
a service technician check the evaporator coils yearly and clean them if necessary.
» The air conditioner thermostat is set too low...Often its
operation is misunderstood. Your air conditioner runs no faster at a lower setting, it only
runs longer. The recommended summer setting is 78 degrees. Set it 2 to 5 degrees higher when
you're away in the day. Recent research in Florida reveals that home cooling costs increase
12% for each degree setting below 78 degrees. Your cooling costs can almost double if you set
the thermostat at 70 instead of 78 degrees!
» The central heat pump is simultaneously cooling and heating...
and the cooling cost triples! Overall this is a rare condition, but memorable to all
involved because the summer bills get so stunningly high. A variety of thermostat and wiring
problems can be the cause. For example, we've found situations where 5,000 watts of supplemental
heating strips come on whenever the air distribution fan runs, winter or summer. The auditor
detects the problem by running the cooling system alone (other appliances off at the breaker
panel) and timing the meter spin to calculate power draw. A 5,000 watt overage is readily detected
by this method.
» Teenagers...
are full-sized human beings who deserve as much respect as people of other sizes and ages,
even if they use a lot of energy per capita but don't yet pay the bills themselves. Small children,
by contrast, are low to the floor and relatively comfortable at levels of summer heat that
stress many adults.
» The thermostat is miscalibrated...
and so is the thermometer on the thermostat faceplate. The system cools lower than the
temperature selected by the resident. For example, the thermostat might be set on 78 degrees,
but an accurate thermometer shows that it's actually cooling to 75 degrees. This is an extremely
common situation - We've found thermostats as much as 10 degrees off. The simplest solution
is to rest an accurate thermometer on top of the thermostat, find out how much it's off, and
compensate accordingly when you select the desired indoor temperature.
» The ceiling lacks adequate insulation...
Heat from the attic is conducting through to the house below. Improving ceiling insulation
is one of the best investments you can make towards lowering your air conditioning costs in
summer. If you're not sure what level of insulation you have in your attic, call us for a free
home energy audit. The older your home, the more likely it is that its original level of insulation
would now be considered inadequate. We still find some older homes with no insulation at all.
» Dogs have pulled air ducts apart beneath the house, cats have bedded
for years in the ceiling insulation, possums have tugged open a crawl way where water pipes
penetrate the floor and they're living in the hollow wall of the bath tub...
and so forth. Energy wise, the worst of these situations is where supply or return
air ducts are disconnected in the crawl space beneath the house. Every summer at least one
of our auditors reports finding the family dog comfortably housed in the return air plenum
under a customer's house. It costs a lot to cool the outdoors!
» The air conditioning system is not getting enough air returned
from the house...
for a variety of reasons. We've seen return air grills set in the floor that are partly
or entirely covered by a rug, for example. In addition to increasing operating costs, inadequate
volume of return air back to the indoor HVAC coil is a major factor in shortening the life
of central air conditioners. Too little air across the indoor coil can potentially lower the
coil temperature to the point of ice formation on the indoor coil. An air conditioner with
its indoor coil covered with ice is in a "destruction mode".
» The HVAC filter is located in a return duct plenum under the house...
and because it's so hard to get to, it's never changed. At some time in the past a
plastic laundry bag was sucked into the return air system and is now plastered against the
filter. Almost every energy auditor can tell of finding situations like this.
» The HVAC air handler, located in a hallway closet, is pulling return
air from the attic as well as the house...
adding considerably to costs. Sometimes this situation is discovered where the resident
previously had a gas or fuel oil furnace in a hallway closet. Originally, the furnace pulled
its combustion air from the attic through an opening in the closet ceiling. When the resident
later switched to a heat pump, the furnace was removed from the closet and replaced with the
heat pump's indoor "blower-coil" unit. But the ceiling opening remained. The new
closet unit was set up to pull return air through a grill in the closet wall into the closet
space, then through a filter mounted in the blower coil unit. But it's pulling air from the
attic as well as the house! Most auditors have a story of first finding this problem when,
with the air conditioner running, they climbed a ladder, lifted the attic hatch and noticed
house air rushing past them into the attic.
» The air conditioning equipment is inefficient...
for a variety of reasons. First, it may have been inefficient from the start. Equipment
ten years old or older is likely to have an original efficiency rating of 7.5 SEER (Seasonal
Energy Efficiency Ratio) or less. Today, Federal law requires manufacturers to achieve SEER
10.0 or higher for all split-system units, and SEER 9.7 for package units. What do these SEER
ratings imply? You've probably already guessed: If your cooling cost is $600 a summer with
a SEER 6.0 unit, your cost would be $300 a summer (for the same amount of cooling) with a SEER
12.0 unit. What other factors affect air conditioning efficiency? The big three are a). dirty
coils, which at normal rates of dirt accumulation degrade efficiency by 5% each year; b). duct
leaks, which in most Florida homes account for about 20% of air conditioning consumption; and
c). improper charge of refrigerant. How common are these types of problems? In 1988 a widely
cited Arizona study of residential air conditioners found the following:
75% of the condenser coils were dirty
70% of the units had improper refrigerant charge
55% of the evaporator coils were dirty
45% had dirty blower wheels
35% had significant duct leakage
10% had a wrong motor or fan installed
» The
HVAC refrigerant charge is low...or it's high. Either way degrades efficiency.
In 1990 a field study of residential central air conditioners found 27% undercharged and
27% overcharged. Overcharging is worse. The unit's cooling ability goes down while the
power draw goes up: The unit runs longer to do the job, and costs more per minute to run.
Overcharging also stresses the compressor, with serious consequences for its lifespan.
The compressor is the most expensive system component to replace.
» The air conditioner's compressor runs all the time...
whether the indoor distribution fan runs or not. Rare.
» The outdoor condenser is located beneath a wooden deck...
and air flow is restricted. In summer, whatever heat is removed from the house by the air
conditioning system is released to the outdoors from the condenser unit--that big metal box
in the back yard. Hold your hand in the hot breeze from the propeller fan--it usually blows
upward--and you'll get the idea. To work well it needs plenty of clearance from decks, bushes
and folded lawn chairs. By the way, that hot air blowing from the outdoor condenser is not
hot air from the house. It's outdoor air heated by passage across the hot condenser coils.
The cleaner those coils are, and the easier it is for the heated air to get away from that
unit, the better it works. Air conditioners and heat pumps only work well if kept clean!
» Leaky supply or return air plenums...
greatly increase the cost of air conditioning. Using blower door technology to test Florida
homes for duct leakage, almost all systems are found to be significantly leaky. The most common
sites of leakage are the supply air and return air plenums, which are the air collecting boxes
on the upstream and downstream sides of the blower-coil unit that distributes air around the
house. In the supply plenum, air pressure is greatest; in the return plenum, air suction is
greatest. Any leakage from these boxes is exaggerated by the extremes of positive or negative
air pressure close to the fan. In the distribution system as a whole, if supply air leakage
predominates, the air pressure in the rooms of the house becomes negative with respect to the
outdoors. If return air leakage predominates, the air pressure in the rooms of the house becomes
positive with respect to the outdoors. A negatively pressured house sucks in warm, moist outdoor
air, burdening the air conditioner; a positively pressured house pushes out expensively cooled
indoor air, losing it to the outdoors. Usually mere duct tape is inadequate to repair these
high pressure plenum leaks--it simply comes loose. Repairs that last use a gluey paste called
mastic, typically having a high content of embedded fiberglass fabric and high tolerance for
variations in temperature.
» In some apartments and town homes, the air conditioner's indoor
component (the blower coil that distributes air to rooms) is located in a small closet,
right over the electric water heater...
which in summer heats the passing air on its way to the a.c. cooling coils and fan.
It helps to lower the water heater's thermostats to the lowest appropriate temperature (usually
115 degrees, or 125 degrees if the resident uses a dishwasher) and insulate the water heater.
» The HVAC system has moisture in the refrigerant...
and efficiency is reduced 5-15%.
» The HVAC system draws warm, moist outdoor air through an unsealed
PVC chase...
that routes refrigerant lines through the slab. Costs rise as the air conditioner works
to cool and dry outdoor air admitted to the system by this and other routes
» The air conditioner's outdoor condenser sits baking in the sun...
increasing its operating cost. A north side location for this unit is recommended.
It's possible to shade it with trees, but remember that the condenser needs plenty of "breathing
room".
» Vines, bushes, tall grass, leaves, litter or lawn chairs cover
the air conditioner's outdoor condenser unit...
so it can't release heat.
» The air conditioner is oversized for the house...
so that it cools powerfully but doesn't run long enough to dry the air. The result
is a cool, damp interior that doesn't feel right. To improve comfort, the resident lowers the
thermostat setting a few degrees and the system runs longer. This dries the air but overcools
it. Costs rise. Everyone should know this about air conditioning: Bigger isn't better. An oversized
air conditioner cycles on-and-off frequently, removes less moisture and wastes energy. A system
correctly sized for your house will run longer for less cost, dry the air better and give greater
comfort than the next bigger size. Correct sizing is a particular concern in Tallahassee where
we experience a very, very, very damp climate.
» Air conditioning supply registers around the house are closed off...
and the house becomes negatively pressured with respect to the out of doors, so that
warm, moist outdoor air is pulled in. Additionally, airflow across the HVAC evaporator coil
is reduced. The system's energy efficiency and cooling capacity are reduced. That is, for a
given amount of cooling work to be accomplished, the system's running cost per minute and the
number of minutes required both increase. Don't close off vents. Repeat: If you have a central
air conditioner or heat pump, don't close off vents. A lot of older federal and state energy
brochures and booklets have advised closing off vents but now we know better. Leave 'em all
open.
» Bedrooms or other rooms are closed off, with no way for air supplied
to the rooms to return (as the air conditioner operates)...
Each closed-off room becomes positively pressured while the remainder of the house areas become
negatively pressured with respect to the outdoors. The result is exaggerated leakage to the
outdoors from positively pressured closed rooms, and from the outdoors into the negatively
pressured house areas. Leakage occurs through bathroom vents, fireplace vents and dampers,
around windows and doors, through recessed ceiling light fixtures, through electric plug and
light switch plates, etc.
» An air conditioning supply duct leads to the garage...
where it simply wastes cool air to the "outdoors".
» The air conditioning system's return air grill is set low on a
wall and blocked by a chair, or its set in the floor where it's covered by a rug...
resulting in restricted return air flow and all the attendant problems
» A small pool or spa is situated literally inside the house...
Rare, but unforgettable. Why not do this? Because of the phenomenal moisture problems that
result, not to mention high air conditioning costs. Remember, the air conditioner works to
remove moisture as well as remove heat. Even in normal circumstances about 38% of the air
conditioner's work (and operating cost) is devoted to moisture removal.
» The customer is attempting to cool the entire house with a variety
of old, inefficient window air conditioners...
Here's a topic that deserves a closer look. Our energy auditors have all observed that
customers with window air conditioners usually have significantly lower bills than those with
central cooling systems. Yes, lower. Why? Because only one or two rooms are being cooled, not
the whole house. However, if four or five old window units are operating all summer to cool
the whole house, then costs get high. Older window units often have energy efficiency ratings
down around 5 EER; newer central systems are at least twice as energy efficient as that.
» The air conditioner's thermostat is near some source of heat...
like a floor lamp. The thermostat gets fooled, it senses heat and calls for the air conditioner
to run.....and run, and run.......Remember, small thermostat adjustments make a big difference
to your cost. If your system cools to 73 degrees instead of 78, your cooling cost rises about
60%.
» The hallway wall behind the thermostat is hot...
because hot air is being drawn down from the attic through that wall cavity whenever the air
conditioner runs. This tricks the thermostat into calling for more and more cooling. Finding
the pathway of air leakage and sealing it cures the problem.
» The area where residents sit down to eat is heated by morning or
afternoon sun streaming through a sliding glass door...
and the whole house is cooled to a very low temperature in order to achieve acceptable comfort
levels at that spot.
» A shade tree was removed...
and air conditioning costs increased by up to 30% compared to last year. Shade is important!
» Air conditioning ductwork in a hot attic is poorly insulated...
Attic heat conducts through to warm the cool stream of duct air.
» The return air plenum box constructed of sheetrock is uninsulated
and leaky and sits in a hot garage...
A fairly common finding.
» All the components of the air conditioning distribution system,
including the air handler, supply ducts and a long return duct, are located in a hot attic...
Lots of older homes have their air conditioning systems configured this way.
» A room or wing or extension was added to the house, or a garage
or porch was enclosed...
and the overall cooling costs go up.
» The
air conditioner's thermostat mounted on the hallway wall is not level...
Behind the thermostat's cover plate its operation usually involves one or two mercury-containing
glass bulbs that tip left or right as the temperature adjustment lever is moved. When you adjust
the lever "downward", calling for cooling, the bulb tilts and a small blob of mercury
rolls over to make an electrical connection. If the thermostat is off-level the mercury roll-over
is affected, and the thermostat's calibration can be thrown off. For example, maybe you've
set the lever to 78 degrees, but because the thermostat isn't level the system cools to 75
degrees. Cooling costs rise by 15% to 24%. Leveling the thermostat is fairly easy using adjustment
screws behind the faceplate, but if you're at all uncertain about it, have it leveled when
your unit is next serviced.
» The residents left town for a summer vacation and were expecting
the next utility bill to be low...
but they left the air conditioner at its normal thermostat setting during their absence and
the weather was hot. For many folks, the best practice is to set the air conditioner's thermostat
up to 83 or 84 degrees when away. The system runs once in a while, preventing indoor humidity
from getting too high.
» House has a package-unit central air conditioner at one end, supply
and return ductwork beneath the house and a garage converted to an uninsulated TV/family
room at the farthest distance from the air conditioner. A couple of ducts are added to
the air distribution system to supply cool air to the family room...
This is a recipe for high bills in summer, but even higher in winter. The ductwork has the
longest possible run--both ways--to cool the room that gets the most evening use. The walls
and ceiling need insulation. The air conditioner's delivery fan is probably not powerful enough
to handle the additional area, and the add-on ducts result in an imbalanced system that no
longer delivers the requisite 400 cubic feet per minute of air (per ton of cooling capacity)
across the air conditioner's evaporator coils. It all adds up to high cooling and even higher
heating costs.
» The air conditioning system is made up of mismatched components...
resulting in greatly lowered operating efficiency. The condenser section and evaporator section
need to be properly matched, as specified by the manufacturer.
» A newly added room is hot so the thermostat setting for the whole
house is lowered...
meanwhile, in the attic, the air supply duct to the new room is laid out and connected to the "boot" above
the register, but was never connected into the main system. By an installation oversight, no
air is delivered to the new room. Surprisingly, most energy auditors have found unconnected
air ducts like this at one time or another.
» The ductwork "boots" behind the registers are loose,
or ducts have fallen away from the boots...
and the system is cooling the crawlspace under the house.
» Flex duct in the attic is kinked or flattened, diminishing air
supply to particular rooms...
and the thermostat setting for the whole house is lowered to compensate. This kind of problem
is especially significant if the rooms having insufficient air supply are the kitchen or family
room. This is a common problem!
» The air delivery system includes some length of panned floor joists
which are leaky...
The spaces between floor joists are sometimes modified for use as return ducts. This cavity
is made into a duct by attaching sheet metal over the bottom of the joists and by capping the
ends of the joist cavity. A leaky panned floor joist draws in air from the crawl space or basement.
To remedy, seal using mastic. The ceiling fans run backwards, breezing upwards. They should
breeze downward, so you feel the breeze.
|